Global Global Algérie Français Algeria English Angola Português Angola English Argentina Español Argentina English Australia English Austria Deutsch Austria English Azerbaijan English Azerbaijan Русский Bahrain English Bangladesh English Belgium English Belgium Français Belgium Nederlands Brazil Português Brazil English Bulgaria български Bulgaria English Cameroon English Cameroon Français Canada English Canada Français Chile Español Chile English China 中文 China 日本語 China English Colombia Español Colombia English Croatia English Czech Republic Čeština Czech Republic English Denmark English Djibouti English Ecuador Español Ecuador English Egypt English Estonia English Ethiopia English Finland Suomi Finland English France Français France English Georgia English Georgia Русский Germany Deutsch Germany English Ghana English Greece Ελληνικά Greece English Guatemala Español Guatemala English Hong Kong, China English Hong Kong, China 中文 Hungary Magyar Hungary English India English Indonesia English Iraq English Ireland English Italy Italiano Italy English Ivory Coast Français Ivory Coast English Japan 日本語 Japan English Jordan English Kazakhstan Русский Kazakhstan English Kenya English Kuwait English Kyrgyzstan Русский Kyrgyzstan English Latvia English Lithuania English Malaysia English Mauritius English Mauritius français (Maurice) Mexico Español Mexico English Moldova Română Moldova English Mongolia English Morocco English Morocco Français Mozambique Português Mozambique English Netherlands Nederlands Netherlands English New Zealand English Nigeria English Norway English Oman English Pakistan English Paraguay Español Paraguay English Peru Español Peru English Philippines English Poland Polski Poland English Portugal Português Portugal English Qatar English Republic of Korea 한국어 Republic of Korea English Romania Română Romania English Saudi Arabia English Serbia Српски Serbia English Singapore English Slovakia English Slovenia English South Africa English Spain English Spain Español Sri Lanka English Sweden English Switzerland Deutsch Switzerland Français Switzerland Italiano Switzerland English Tanzania English Thailand ไทย Thailand English Togo English Togo Français Tunisia English Tunisia Français Türkiye Türkçe Türkiye English Turkmenistan Русский Turkmenistan English Ukraine Українська Ukraine English United Arab Emirates English United Kingdom English Uruguay Español Uruguay English USA English Uzbekistan English Uzbekistan Русский Vietnam Tiếng Việt Vietnam English

Watertightness Testing of Bituminous Waterproofing Membranes: Standards, Methods and Acceptance Crit

Watertightness (impermeability) testing is a mandatory quality control test for bituminous waterproofing membranes, verifying their ability to resist water penetration under sustained hydrostatic pressure. This article explains the testing principle, applicable standards such as GB/T 328.10, EN 1928 and ASTM D5385, specimen preparation, step-by-step test procedures, pass/fail criteria and typical applications in roofing and underground waterproofing projects.

Technical Overview

Watertightness, commonly referred to as impermeability, is the ability of a bituminous waterproofing membrane to prevent the passage of water through the sheet when exposed to a sustained hydrostatic pressure for a defined period of time. For bituminous (asphalt-based) membranes such as SBS- or APP-modified bitumen rolls, watertightness is a pass/fail index required by virtually every product standard, because coating voids, pinholes, thin coating sections or damaged reinforcement cannot be reliably detected by thickness and mass measurements alone.

The test is performed by clamping a conditioned specimen over a perforated support plate inside an impermeability tester, applying water pressure to the service face of the specimen, and observing the underside for any sign of seepage. Testing is typically carried out by manufacturers' quality control laboratories, accredited third-party laboratories, and engineering supervision units responsible for construction acceptance.

  • GB/T 328.10-2007 — Test methods for building sheets for waterproofing, determination of watertightness of bituminous sheets
  • EN 1928 — Flexible sheets for waterproofing, determination of watertightness of bitumen, plastic and rubber sheets
  • ASTM D5385 — Hydrostatic pressure resistance of waterproofing membranes
  • Product specifications such as GB 18242, GB 18243, GB 326, GB 23441 and EN 13707, which define the required pressure and duration for each membrane type

Testing Samples

Specimens shall be cut from positions distributed across the full width of the roll, at least 1 m away from the outer end of the roll. A minimum of three specimens is normally required, each large enough to cover and be clamped over the perforated plate (typically 150 mm × 150 mm). All specimens are conditioned at (23 ± 2) °C before testing, and the face intended to be exposed to water in service is clearly marked.

SBS-Modified Bituminous Waterproofing Membranes

Styrene–butadiene–styrene (elastomeric) modified bitumen membranes with polyester or composite reinforcement, typically 3.0 mm to 5.0 mm thick, are the most widely sampled products. They are specified under GB 18242 and are used for exposed and protected roofs, basements and civil structures. The watertightness requirement is defined by the product grade, commonly on the order of 0.2 MPa to 0.3 MPa held for 30 minutes or longer.

APP-Modified Bituminous Waterproofing Membranes

Atactic polypropylene (plastomeric) modified bitumen membranes, specified under GB 18243, offer superior high-temperature stability and are frequently used for exposed roofing in hot climates. The same impermeability test method applies, with the pressure–time combination set by the product standard and the design specification.

Self-Adhesive and Pre-Applied Bituminous Membranes

Cold-applied self-adhesive bituminous membranes (for example under GB 23441) and pre-applied sheets for blind-side waterproofing are also tested for watertightness. Release liners must be removed before clamping, and care must be taken to prevent adhesive contamination of the sealing gaskets, which could mask a genuine coating defect.

Bituminous Base Sheets and Roofing Felts

Base sheets, saturated felts and underlay layers for built-up roofing systems are verified at the lower pressure levels specified for their product class. Because these products carry thinner bitumen coatings, watertightness testing is particularly sensitive to coating continuity and saturation quality.

Testing Items

The core testing item is watertightness under specified hydrostatic pressure and duration. Depending on the purpose of the evaluation, the following items are typically covered:

  • Watertightness at the specified pressure and time — pass/fail verification of water penetration through the sheet
  • Maximum sustained hydrostatic pressure — determination of the highest pressure the membrane withstands without leakage, relevant for permanent water head exposure
  • Leakage location and failure mode — identification of coating pinholes, thin sections or exposed reinforcement
  • Watertightness after conditioning or artificial ageing — verification that impermeability is retained after heat ageing or UV exposure
  • Companion quality indices — tensile strength and elongation, low-temperature flexibility, heat resistance, dimensional stability and lap peel strength, which are usually tested together for full product conformity

Testing Methods

Apparatus and Specimen Preparation

The impermeability tester consists of a sealed water chamber fitted with a perforated metal support (commonly a seven-hole disc), annular rubber gaskets, a calibrated pressure gauge and a pump or gas-loaded accumulator capable of maintaining a constant pressure. The chamber is filled with clean water at (23 ± 2) °C and all trapped air is expelled. Each conditioned specimen is placed with its marked service face toward the water and clamped so that the gasket seals only the outer edge of the specimen.

GB/T 328.10-2007 Hydrostatic Method

This is the reference method for most Chinese product standards and engineering acceptance procedures:

  • Place the specimen on the perforated plate with the service face in contact with water and clamp the cover plate firmly.
  • Increase the water pressure gradually to the specified value, commonly between 0.2 MPa and 0.4 MPa depending on product class, typically within 5 to 10 minutes.
  • Maintain the pressure constant within ±5% for the specified duration, typically 30 minutes and up to 120 minutes for higher grades.
  • Observe the underside of the specimen continuously throughout the holding period.
  • The result is a pass when no specimen shows water seepage, droplets or wetting on the underside.
  • Record the pressure, duration, temperature and the exact position of any leakage for failure analysis.

EN 1928 Methods

EN 1928 defines two procedures for flexible waterproofing sheets. Method A applies a low water pressure, equivalent to a 2 kPa water head, for 24 hours and is intended for roof membranes subjected to intermittent water exposure. Method B applies an elevated hydrostatic pressure, frequently specified at 60 kPa, for 24 hours and is used where a higher resistance must be demonstrated, such as under permanent water head. In both methods the underside of the specimen is examined for visible water drops, and any penetration constitutes failure.

ASTM D5385 Hydrostatic Pressure Resistance

ASTM D5385 evaluates the resistance of waterproofing membranes to water under pressure. The specimen is clamped over a test chamber, the hydrostatic pressure is increased in controlled increments and held at each level, and the membrane is observed for leakage. The test reports the maximum pressure sustained without water penetration and is widely used for below-grade waterproofing membranes exposed to continuous hydrostatic head. ASTM D751 hydrostatic (Mullen) resistance may be used as a related screening test for reinforced coated sheets.

Judgment and Reporting

The pass criterion is the absence of any visible water penetration on the underside of the specimen during the entire pressure-holding period. Water droplets or continuous seepage indicate failure. Care must be taken to distinguish genuine leakage from condensation caused by ambient humidity. The test report shall include the standard applied, specimen identification and position within the roll, the tested face, pressure, duration, temperature, individual results for each specimen and any deviations from the standard procedure. Central leaks generally indicate coating voids or pinholes, while edge leaks often point to gasket sealing problems rather than a material defect.

Applications

  • Factory quality control and type testing of membrane production lines, ensuring coating continuity before rolls are released to market
  • Third-party conformity assessment, product certification and market surveillance sampling
  • Construction acceptance, including witness sampling and re-testing of rolls delivered to the project site
  • Roofing systems, both exposed and protected, where membranes must withstand standing water and melting snow
  • Underground engineering such as basements, tunnels and metro structures exposed to permanent groundwater head
  • Civil structures including bridge decks, podium slabs, planters, plazas and water features
  • Research and development, formulation comparison, verification of watertightness after artificial ageing, and failure diagnosis for warranty claims and engineering arbitration

FAQ

What pressure and duration are normally required for modified bitumen membranes?

Most product specifications require 0.2 MPa to 0.4 MPa held for 30 minutes, with higher grades and thicker membranes often requiring up to 120 minutes. The exact pressure–time combination is defined by the applicable product standard and the project specification.

How many specimens are tested and where are they taken from?

At least three specimens are cut from positions distributed across the full roll width, at least 1 m from the outer end of the roll, and conditioned at (23 ± 2) °C. Each specimen is tested once and all must pass for the sample to be accepted.

What is considered a test failure?

Any water droplet, continuous seepage or visible wetting on the underside of the specimen during the pressure-holding period constitutes failure. Condensation caused by ambient humidity is not counted, but it must be clearly distinguished from genuine penetration and documented.

Which face of the membrane should contact the water?

The face that will be exposed to water in service, usually the upper face of the membrane. If the service face is not specified by the manufacturer or the product standard, both faces may be tested for information purposes.

Are GB/T 328.10 and EN 1928 results directly comparable?

No. GB/T 328.10 uses relatively high pressures over short durations, while EN 1928 applies lower pressures over 24 hours. Both methods verify watertightness, but results must always be reported against the specific method referenced in the specification.

Can watertightness be verified on the construction site?

The laboratory impermeability test applies to material samples taken from delivered rolls. On site, the installed waterproofing system is commonly verified by a flood or ponding test of the finished membrane before it is covered, in accordance with the project quality plan.

Does a passing watertightness test guarantee long-term performance?

It confirms coating continuity and resistance to the specified static water head at the time of delivery. Long-term performance additionally depends on ageing resistance, lap joint quality and installation workmanship, which are verified through the companion physical property tests and site inspections.